57 ALKALINITY CONTROLLER

 

ALKALINITY CONTROLLER is a concentrated alkaline treatment for pH control in boilers.

How does it work?

ALKALINITY CONTROLLER should be used as part of a coordinated treatment programme in conjunction with other AQUAMARINE B.W.T. products.

ALKALINITY CONTROLLER provides the alkaline conditions that allows HARDNESS/PHOSPHATE CONTROL to operate effectively. This is done by neutralising any acidic conditions and maintaining alkalinity within optimum limits.

The product is suitable for use with all boiler pressures.

Results of use

ALKALINITY CONTROLLER helps to keep magnesium and calcium salts in suspension and helps in maintaining efficiency and reducing maintenance.

Dosing and Sampling

For optimum results dose directly into the boiler via the bypass pot feeder installed in the boiler water feed line.

A representative sample of boiler water must be taken at regular intervals (daily or every 3 days), at a frequency adequate for the type of boiler. The sample should be taken immediately following blow down and should be analysed immediately.

Follow the AQUAMARINE test kit instructions and record the results on the log sheets provided by AQUAMARINE. These should be returned monthly for review by AQUAMARINE CHEMICALS.

The results indicate the level of P Alkalinity in the boiler. Use the dosage chart below to adjust the levels of treatment required.

USING THE TABLE: Select the section corresponding to the pressure of the boiler to be treated and read across the table to obtain the level of treatment required.

ALKALINITY CONTROL
DOSAGE-ML/TONNE FOR DISTILLED WATER
BS1170
P. Alkalinity test result in ppm
GROUP BOILERS 0-60 60-90 90-100 100-110 110-120 120-150 150+ Range mls / tonne
1 180 90 60 <- - Satis-factory No dose> Blow-down 100-150 225
2 180 90 60 <- - Satis-factory No dose> Blow-down 100-150 225
3 150 65 50 <Satis-factory No dose>   Blow-down 100-130 200
4 135 65 <- - Satis-factory No dose> <Blow down> 90-120 180
                   

BS1170 Group Boilers 1 Pressure Range 0-17.5 Bar 0-258 Psi

BS1170 Group Boilers 2 Pressure Range 17.5-31 Bar 258-455 Psi

BS1170 Group Boilers 3 Pressure Range 31-42 Bar 455-618 Psi

BS1170 Group Boilers 4 Pressure Range 42-60 Bar 618-880 Psi

Normally: 0.18 litre/tonne of ALKALINITY CONTROLLER will raise p.Alkalinity by 100 ppm. Proper treatment should normally give a pH between 9.5 and 11. These are recommended limits for levels of treatment. They are not intended to replace either shipping company instructions or boiler manufacturers policy.

Summary

ALKALINITY CONTROLLER is a part of a coordinated programme of Boiler Water Treatment yielding the basic alkalinity upon which successful boiler water treatment depends.