4 CORROSION CONTROLLER 30

 

Liquid cooling water corrosion and scale inhibitor

Description

Aquamarine Corrosion Controller is an easy to use concentrated liquid that inhibits electrolytic corrosion, cavitational corrosion and controls scale and sludge. It is also compatible with a wide range of hoses, gaskets and seals.
Aquamarine Corrosion Controller passivates metal surfaces and combines with sludges, scale and rust deposits to allow their gradual removal. It is suitable for low, medium and high speed engines.

To clean out a cooling water system which has been treated previously with another chemical or has oil or scale contamination use the Diesel engine cooling water Inline Cleaner (Product No 16).

For oil only contamination use the aquawash in circulation at a dilution of 0.5 and 7 litres per tonne of cooling water dependant on degree of contamination. Circulate for 1-2 hours, flush and then flush with clean water.

Uses

Aquamarine Corrosion Controller should be fed directly by the bypass pot feeder to the main circulating line or into the cooling water expansion tank.

(For systems using totally de-ionised water raise nitrite levels to 1700 p.p.m. as corrosion is more likely.)

Control is based on nitrite concentration and additions should be made after representative sampling. Aquamarine test kit is supplied for accurate checking.

Target = 1500 p.p.m.

 
Nitrite p.p.m. 0 500 1000 1500
Ltrs/1000 Ltrs make up 3.3 2.2 1.1 0

 

Try to keep Nitrites within the parameters discribed. Low Nitrite levels will give rise to an unprotected system and ultimately corrosion problems.

Log sheets should be returned to Aquamarine on a monthly basis for analysis.

25 Litre Pack Size

NATO STOCK # JO13 6850-992392381